LS cast resin transformer takes pride in the ability to offer a wide variety of designs and configurations necessary to satisfy customer needs. Computer and CAD/CAM systems are used for quick and accurate design and manufacturing to meet specific customer requirements.
| Rating | Specification | |||
|---|---|---|---|---|
| Installation place | Indoor(Enclosure needed for outdoor) | |||
| Applicable standard | KS C 4311, IEC 60076-11, IEEE C57.12.01 | |||
| Frequency | 60, 50 | |||
| Insulation kind | F type, H type | |||
| Coil temperature rise | 100K, 125K | |||
| HV rated voltage(kV) | 33, 22, 10, 6 | |||
| HV tap voltage(V) | 5 Taps (±2×2.5%) | |||
| LV rated voltage | 400V | |||
Customized Winding Connection | Dyn11 | |||
| Impulse withstand voltage(kV) (HV/ LV) | 145 / – 170 / – | 95 / – 125 / – | 60 / – 75 / – | 40 / – 60 / – |
| Normal frequency withstand voltage(kV) (HV/ LV) | 70 / 3 | 50 / 3 | 28 / 3 | 20 / 3 |
| Rated capacity (kVA) | up to 3150 | |||
| Enclosure | IP 2X, IP 3X, IP 4X | |||
※ The above descriptions are standard specifications, but other specifications are available according to orders. (~36kV, ~25MVA)
Saya System Tavatav Inc.
LS spun off from LG in 2003. LS is made up of several companies operating in the Energy, Electric, Electronic and Material sectors.